The flammable gas detector has a standard method to confirm the state of the sensor, as if it is to determine how much oil is in the fuel tank inside the car. It is called the retention value. The retention value is a measure of the sensitivity of the sensor and is derived when the gas detector is calibrated.
At the end of the gas detection calibration, the retained value of each sensor is displayed and stored in the instrument’s calibration record. When the sensor’s retention value is less than or equal to 50% of the calibration gas concentration, the sensor will fail to be calibrated and must be replaced.
When the retention value is between 50% and 70% of the calibration gas concentration, it indicates that the sensitivity of the sensor is at the edge state, and the replacement of the gas sensor can be considered at this time.
Simply say, when the flammable gas detector needs to be replaced, as long as the gas sensor has sufficient sensitivity or retention value to successfully calibrate, the flammable gas detector can be used normally. It is not necessary to replace the sensor until the sensor calibration fails.
Of course, the above is only the replacement cycle of our flammable gas detector under normal circumstances. It does not rule out some other faults in the flammable gas detector. If our flammable gas detector fails, it is recommended to contact the manufacturer in time. The manufacturer will according to your fault. The situation gives you the appropriate repair or replacement solution.
Focus on security technology innovation and lead the development of AI industry. The 17th China I...
On May 11, 2019, our company Yaoertai was founded 14th anniversary! In the past 14 years, we hav...
Saturday, the first week of work in 2019, On a sunny afternoon, Yaoertai, all business colleagues...
The 28th China (Beijing) International Building Decoration and Materials Expo will be held on Mar...
The 15th R + T Asia Shanghai Door and Window Sunshade Exhibition will be held from February 27th ...
The frequency used by the radio remote control is 433Mhz or 315Mhz, also referred to as 433 remot...
The infrared alarm can detect the infrared rays emitted by the human body, and is composed of an ...
Congratulation YET Global Sources Electronics Exhibition bring to a successful close Gate remote ...